Case: T11DV06162
Case Details
Entered Date:
08/02/2011
Applicant:
QUENTIN ROBERT & NIHLA H THOMSON REVOCABLE TR
Description:
TFD EMERGENCY CALL-OUT RESIDENTIAL ELECTRICAL FIRE.
Case Violations
Case Number: T11DV06162
Case Status: COMPLIAN
Case Description: RESIDENTIAL FIRE
Total Violations: 1
| Violation Date | Code Statue |
|---|---|
| 09/08/2011 | T.C. Ch. 16, Sec. 16-13(b) ACCUMULATION OF REFUSE PROHIBITED. Each owner, lessee, tenant, resident or occupant shall maintain a property so it is free of accumulated refuse and debris. Accumulated refuse and debris means contained or uncontained refuse and debris that is present on the property in a manner not authorized by the Tucson Code. Material recycling facilities meeting the requirements of section 15-24.7 are exempt from this prohibition. |
Outstanding Inspections
Case Number: T11DV06162
Case Status: COMPLIAN
Case Description: RESIDENTIAL FIRE
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2011 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | JHURD | Item closed | |
| 09/08/2011 | NPO(HC)-COOLING | JHURD | Item closed | |
| 09/08/2011 | NPO - INT. BUILDING MAINTENANC | JHURD | Item closed | |
| 10/25/2011 | NPO - REFUSE/TRASH/DEBRIS | JHURD | Item closed |
Completed Inspections
Case Status: COMPLIAN
Case Number: T11DV06162
Case Description: RESIDENTIAL FIRE
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2011 | INSP - INITIAL CODE ENFORCMENT | GGOODMAN | Approved | VISITED SITE, MET WITH TFD CAPT. TONY GONZALEZ WHO MENTIONED THAT UPON ARRIVAL THEY FOUND SMOKE BILLOWING OUT OF THE INTERIOR SUB PANEL AND THAT THE WALL SECTION BELOW THE PANEL WAS HOT TO TOUCH. FOUND TWO LIFELINES RUNNING FROM THE TRAILER TO AN OLDER BOX ON A POST BEING USED AS A PEDESTALL, THEY UNPLUGGED BOTH LIFELINES. TFD INFORMED THE OCCUPANTS THAT THEY WOULD NOT BE ABLE TO STAY AT THE TRAILER AND TFD CONTACTED RED CROSS TO PUT THE TENANTS UP UNTIL REPAIRS COULD BE MADE. OCCUPANTS INFORMED ME THEIR LOT WAS CONSIDERED LOT #B AND THAT SERVICE PANELS THAT PROVIDED POWER TO THEIR LOT WAS INSTALLED NEXT DOOR. WALKED OVER TO THE NEIGHBORING PROPERTY FOUND (3) 100 AMP SERVICE PANELS, ONE FED LOT B, ONE FED LOT #A, AND THE THIRD PANEL FED THE HORSE CORRALS. CALLED TEP TO TURN OFF DISCONNECT INSIDE THE PANEL AND ASKED THEY PUT A LOCK ON THE BOX. ** FOUND BARE WIRE, BURNED WIRING AND BREAKERS INSIDE THE INTERIOR SUB PANEL DUE TO ARCHING. FOUND IMPROPER INSTALLATION OF THE "PEDESTAL" WHICH FED THE A/C UNIT AND THE INTERIOR SUB PANEL. EMERGENCY VACATE NOV WAS ISSUED FOR THE HAZARDOUS ELECTRICAL AND NO A/C AND INCLUDED THE DETERIORATED FLOORING INSIDE THE UNIT. *RESEARCH FOUND THAT THE (3) SERVICE PANEL LOCATED UNIT # A WERE NEVER PERMITED, CONTACTED OWNER ANN THOMSON INFORMED HERE A PERMIT WOULD BE REQUIRED FOR THE (3) SERVICE PANELS BEFORE SHE COULD MOVE FORWARD WITH THE WORK AT UNIT # B. OWNER INFORMED ME THAT SHE ALREADY APPLIED FOR AN ELECTRICAL REPAIR PERMIT. OCCUPANT: RAYMOND CASSILLAS 251-3176 OWNER: ANN THOMSON 561-7660 |
| 10/25/2011 | INSP - FOLLOW UP CODE ENFORCE | JHURD | Approved | VISITED SITE: ALL YARDS CLEANED OF TRASH/DEBRIS, OVERGROWN VEG. COMPLIANT ON THESE ISSUES: SEE COND. RESEARCH PERMIT ISSUE. |
Completed Activity Special Conditions
Case Description - RESIDENTIAL FIRE
Case Number - T11DV06162
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 6
| Date | Name |
| 09/12/2011 | CONTACTED BY MAILING |
| 08/08/2011 | NOTICE AND ORDER ISSUED |
| 08/08/2011 | NOTICE OF VIOLATION ISSUED |
| 10/31/2011 | VIOLATION CLOSED |
| 10/26/2011 | RESEARCH |
| 08/08/2011 | 8-5 CITY COMM EMERGENCY |