Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2011 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE, MET WITH TFD INVESTIGATORS, THEY MENTIONED THAT FIRE HAD STARTED IN THE S/W BEDROOM. FURTHER INSP BY TFD FOUND SMALL DRYER APPLIANCE CONNECTED TO A 50 FT CORD HAD ARCHED AT THE APPLIANCE/ CORD CONNECTION, CORD HAD NEW FEMALE END. END HAD BEEN REPLACED. CORD WAS KICKED UNDER THE BED WHICH CAUGHT FIRE WHEN THE APPLIANCE ARCED. TFD BROKE WINDOW AND CUT A HOLE IN THE ROOF/CEILING. TEP ARRIVED ONSITE AGREED THERE WAS NO REASON TO CUT POUER. S/W GAS ARRIVED ONSITE CONDUCTED LINE TEST AND CHECKED OUT APPLIANCES. CHECKED OUT OK. *INTERIOR OF STRUCTURE HAD A MINIMUM ONE INCH OF WATER THRU OUT THE STRUCTURE. *HEAVY SMOKE DAMAGE THRU OUT. * NEW GAS PACK INSTALLED ON THE ROOF WITHOUT PERMIT (CHECKED P+ AT LATER DATE) *ELECTRICAL SERVICE PANEL HAS MISMATCHED BREAKERS INSTALLED,ONE OR TWO INSTALLED INCORRECTLY. INTERIOR SUB-PANEL BURIED INSIDE KITCHEN CABINET. EXPOSED WIRING AT THE FAN ABOVE STOVE. EMERGENCY ORDER TO VACATE ISSUED FOR UNSAFE ELECTRICAL, UNSANITARY CONDITIONS (WATER AND SMOKE DAMAGE) , AND FIRE DAMAGE |