Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2011 | INSP - INITIAL CODE ENFORCMENT | Approved | TFD CALLOUT FOR HOUSE FIRE. ONSITE WITH TEP, TFD LEFT SITE. FIRE AT WOODEN PEDISTAL. PEDISTAL IS LEANING DUE TO ROTTING AT GROUND LEVEL. NEEDS REPLACEMENT. OVERHEAD ELECTRICAL DROP HAS TREE LIMBS LEANING AGAINST IT. NO DISCONNECT FOUND AT METER, OLD DISCONNECT PANEL FOUND ON THE GROUND, REPLACED BY JUNCTION BOX. MAIN FEED TO 100 AMP SUBPANEL IN KITCHEN BETWEEN COUNTER TOP AND CABINETS. LACKING 3' CLEARANCE. NO GROUND FOUND, NO BONDING, UNDERSIZED WIRNG, DOUBLE LUGGING AT ALL BREAKERS. 100, 60 AND A 15 AMP BREAKER ALL DOUBLE LUGGED. 60 AMP DOUBLE LUGGED POWERING HOTWATER HEATER,100 AMP BREAKER POWERING DRYER. THIS MAIN 100 AMP PANEL IS FEEDING A 60 AMP IN BEDROOM CLOSET. METER PULLED AND CAPPED NO POWER ALLOWED UNTIL NEW WEATHER HEAD AND SERVICE DROP WITH UPGRADE IS COMPLETED WITH PERMITS. OWNER CALLED OUT AND SIGNED NOV. UNIT IS COMDEMED DUE TO HAZ ELECTRICAL. OVER FLOWING SEPIC FOUND ON SITE. i NEED TO CONFIRM WITH PIMA COUNTY TO SEE IF THEY WILL REQUIRE A NEW CONNECTION TO SEWER. |