Description:

ELECTRICAL FIRE

Completed Inspections

Case Status: COMPLIAN
Case Number: T11DV01644
Case Description: EMERGENCY
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/16/2011 INSP - INITIAL CODE ENFORCMENT MROMERO Approved TFD CALLOUT FOR HOUSE FIRE. ONSITE WITH TEP, TFD LEFT SITE. FIRE AT WOODEN PEDISTAL. PEDISTAL IS LEANING DUE TO ROTTING AT GROUND LEVEL. NEEDS REPLACEMENT. OVERHEAD ELECTRICAL DROP HAS TREE LIMBS LEANING AGAINST IT. NO DISCONNECT FOUND AT METER, OLD DISCONNECT PANEL FOUND ON THE GROUND, REPLACED BY JUNCTION BOX. MAIN FEED TO 100 AMP SUBPANEL IN KITCHEN BETWEEN COUNTER TOP AND CABINETS. LACKING 3' CLEARANCE. NO GROUND FOUND, NO BONDING, UNDERSIZED WIRNG, DOUBLE LUGGING AT ALL BREAKERS. 100, 60 AND A 15 AMP BREAKER ALL DOUBLE LUGGED. 60 AMP DOUBLE LUGGED POWERING HOTWATER HEATER,100 AMP BREAKER POWERING DRYER. THIS MAIN 100 AMP PANEL IS FEEDING A 60 AMP IN BEDROOM CLOSET. METER PULLED AND CAPPED NO POWER ALLOWED UNTIL NEW WEATHER HEAD AND SERVICE DROP WITH UPGRADE IS COMPLETED WITH PERMITS. OWNER CALLED OUT AND SIGNED NOV. UNIT IS COMDEMED DUE TO HAZ ELECTRICAL. OVER FLOWING SEPIC FOUND ON SITE. i NEED TO CONFIRM WITH PIMA COUNTY TO SEE IF THEY WILL REQUIRE A NEW CONNECTION TO SEWER.
04/13/2011 INSP - FOLLOW UP CODE ENFORCE MROMERO Approved FU SHOWS , NEW 100 AMP SYSTEM DONE WITH PERMIT. AND SEPTIC HAS BEEN PUMPED. VIOLATIONS ABATED. CLOSE.