Permit: T11CM03396

Parcel: 130170950


Addresses:

4043 E 26TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
02/02/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
01/31/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WIRING/ROMEX IN STORAGE ROOM NOT TO CODE-LOOSE RECEPT HANGING BY CABLE, BROKEN PORCELAIN FIXTURE, UNSUPPORTED CABLES, ROMEX BELOW 8' TO BE PHYSICALLY PROTECTED
2) CKT BREAKERS TO BE OF SAME MANUFACTURE AS PANEL PER LISTING INFO ON INSIDE COVER
3) LOAD CONDUCTORS MUST BE IN APPROVED RACEWAY, TERMINATED TO SUB PANEL
4) LABEL OLD SUB PANEL AS J-BOX
01/26/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920*
1) NO ACCESS TO SITE
01/25/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUB PANEL TO BE J-BOX AND MAIN PANEL OUTSIDE BREAKERS TO HANDLE BRANCH CIRCUITS
11/23/2011 ELECTRIC - RECONNECT Denied 1. SUBPANEL REQUIRES (4) WIRE PULL - NEED EQUIPMENT GROUNDING CONDUCTOR.
2. ALL EQUIPMENT GROUNDS & NEUTRALS NEED TO BE SEPARATED AT SUB PANEL BUS BAR
3. GROUNDING ELECTRODE CONDUCTOR NEEDS TO HIT GROUND RODS FIRST, THEN GAS LINE BOND
4. SECURE GROUND TO WALL UNDER PANEL
5. PUT ADDRESS ON PANEL
11/08/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAIN SERVICE HAS BEEN ALTERED-NEED TO PERMIT NEW WORK
2) NEW GROUND RODS NEED TO BE MINIMUM 6' APART
3) PUT ADDRESS ON NEW PANEL
4) SMOKE DETECTORS NEED TO BE 3' AWAY FROM REGISTERS-INSTALL PER MANUFACTURES SPECS
10/28/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEVERAL HAZARDS AT MAIN NEED TO BE ADDRESSED, CONDUCTORS DBL LUGGED, FUSES BROKEN, ROMEX EXPOSED, NO GROUNDING SYSTEM AND ADDED DISCONNECT
2) MIS MATCHED (2) AND (3) PRONG OUTLETS THRU OUT
3) NEED SMOKE DETECTORS IN ALL SLEEPING ROOMS/HALL
4) ALL ELECTRICAL MUST BE SAFE TO RELEASE