Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2012 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/20/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE DOCUMENTED PROCEDURE OF STERILIZATION 2) INSTALL BEVERAGE EQUIPMENT AND DRAINS 3) SUPPORT BACKFLOW DEVICES, PIPE RELIEF DRAINS SEPERATE CONDENSATE FROM ICE BIN DRAIN 4) PROVIDE A MINIMUM 1" AIR GAP ON ALL REQUIRED DRAINS, RELIEF VALVE AND ICE BIN-INDIRECT DRAINS 5) REPAIR DAMAGED VENTS AND CAP ABANDONED VENT 6) PROTECT VENTS FROM UV AND INSTALL LEAD FALSHINGS OR PROVIDE LETTER FOR ALL CAHNGES OF PLAN SPECS 7) HAMMER ARRESTORS REQUIRED AT WB 8) INSTALL EXP TANK AFTER CHECK VALVE 9) PROVIDE PROPER SOAP DISP CONNECTION 10) AN AVB MAY NOT HAVE VAVLES DOWNSTREAM |
|
| 01/19/2012 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TEMP C OF O |
|
| 01/17/2012 | PLUMBING - FINAL | Cancelled | CANCELLED PER CONTRACTOR STEVE #272-0621 | |
| 01/17/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/13/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |