Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T11CM03219
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/09/2012 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
12/15/2011 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPLAINED TO STEVE 272-0621 THAT ENGINEERING IS REQUIRED TO CHANGE TYPE OF HYDRO MECHANICAL INTERCEPTOR AND THAT I CANNOT GIVE ANY APPROVAL WITHOUT A CITY APPROVED REVISION 2) FLOW CONTROL MAY NOT BE BURRIED BELOW SLAB 3) A 3 X 2 RESTRICTION AT OUTLET IS A CODE VIOLATION 4) INTERCEPTOR REQUIRES A VENT 5) PLEASE HAVE ALL OF YOUR CHANGES REVISED AND APPROVED 6) PROVIDE REVISION TO PLUMBING INSPECTOR |
|
12/13/2011 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/29/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) INSTALLED PER RED LINES WITH 2" GW FOR 3 FIXTURES 2) PROVIDE REVISION PRIOR TO FINAL 3) PROVIDE A 2" INTERGAL FLOW CONTROL INTERCEPTOR |
|
11/28/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) SOIL PIPING WITH TEST OK, CORRECT VENT 90 AND VENT TAKE OFF 2) COMPLETE GW CHANGES AND RED LINE ALL CHANGES TO PLAN 3) SUPPORT PIPING CONTINOUSLY |