Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM02899

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/20/2012 MECHANICAL - FINAL Partial Approval 1. TYPE EXHAST FANS POINT OF DISCHARGE IS TO BE NO LESS THAN 40" FROM ROOF SURFACE PER IMC
2. EXTEND ELECTRICAL WHIPS TO ACCOMDOATE FAN ELEVATION AWAITING DUCT SMOKES DETECTOR TESTING PRIOR TO TEMP C.O ALL ELSE OK