Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM02899

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2012 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/25/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 4" PVC DRAIN FOR FUTURE TENANT, NEXT TO HAIRCARE OK TO BACKFILL
2) TRENCH DRAIN AT G.M. VESTIBLE CART STORAGE OK TO COVER
05/23/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) TRENCH DRAIN AT G.M. VESTIBULE OK TO COVER
2) TRENCH DRAIN INSTALLED AT CART STORAGE AND TESTED OK
3) PHARMACY PLUMBING OK TO COVER
05/21/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) SOIL PIPING FROM GRID LINE D TO HCS CONNECTION AND BRANCHES TO COL 7.4 WITH TEST OK
05/18/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PIPE SIZES AT SS SEWER TO MATCH PLANS
05/17/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
05/10/2012 PLUMBING - ROUGH, SOIL Partial Approval 1) WATER TEST FOR DWV, OR PARTIAL, IS MINIMUM TEN FEET HEAD
2) VENTS BELOW THE FLOOD RIM TO HAVE 2 PERCENT PITCH
3) AT HAIR CARE UNDER FLOOR OK TO COVER
4) 4" SS SEWER EXTENDED TO POC WITH 6" OK
05/09/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
05/03/2012 PLUMBING - ROUGH, SOIL Partial Approval 1) SANITARY SEWER, FUTURE TENANT STUBS AND OTHER BRANCHES TO COLUMN G-7 AT FRONT OF STORE OK TO COVER
04/27/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) SANITARY (CWV) SEWER AND GREASE WASTE BRANCH PIPING EAST HALF OF BLDG (GROCERY AREA) OK TO COVER COLUMN LINE #4 EAST AND #A-K
04/26/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) NORTH SIDE SANITARY WASTE UNDER SLAB TEST OK
04/20/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) GW DELI AND BAKERY
04/17/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) CORRECTIONS FROM 04/13/12 MADE OK. OK TO COVER
04/13/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) GROCERY CASES BETWEEN COLS 1 AND 2 TRAPS WITH REDUCERS OK EXCEPT 1 LEAK
2) FS1 OFF OF 6" MAIN; BRANCH CONNECTION REQUIRES A CORRECTION
3) CONNECT BRANCH TO MAIN HORIZONTALLY
4) UPC 910.5 DOES NOT ALLOW VERTICAL CONNECTION
3)
04/11/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) RECEIVING DWV #7 AND AQUARIUM SOIL WITH TEST OK
04/05/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 6" X 300' AIR TEST FOR 5 MINUNTES AND 40 SECONDS WITH NO DROP OK
2) 6" X 140' AIR TEST FOR 5 MINUTES AND 40 SECONDS WITH NO DROP OK
3) PVC BLDG DRAIN FOR BREAKROOM OK
4) FROM BATHROOM TO BREAKROOM OK
03/27/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) SANITARY WASTE FROM AUTO CARE AND GREASE INTERCEPTOR TO COLUMN #7 OK TO COVER
2) WATER TEST 1 RISER TO 10'
03/23/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
03/15/2012 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) GREASE WASTE UNDER BLDG OK TO COVER
2) C.W.V. IN GROCERY AREA MAIN ONLY
3) BRANCHES TAKEN OFF OF MAIN AT 45 DEGREE OK PER RON BOOSE
03/14/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) SEE 2006 UPC ILLUSTRATED TRAINING MANUAL CWV
2) CWV SYSTEM IS DESIGNED TO BE FLAT, WITH DRAINAGE ALONG THE BOTTOM AND VENTING ALONG THE TOP OF THE PIPE. ALL BRANCH CONNECTIONS TO BE MADE FROM THE SIDE AND ONE 45 DEGREE OFF SET ALLOWED ALONG THE BRANCH TO MINIMIZE TAIL PIECE LENGTH
3) GREASE WASTE MAIN TO WITHIN 10' OF EXTERIOR WALL
4) OK TO COVER ?
03/09/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*