Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T11CM02899
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2012 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
06/26/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* OK TO POUR BOTH SIDES BACK OF HOUSE SOUTH OF ? OK TO GROUT 2ND LIFT AT NORTH ENTRANCE |
|
06/22/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 2 COLUMNS CN EXTERIOR WEST SIDE NEAR AUTO BAY ENTRANCE OK TO GROUT AND CAP |
|
06/20/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 3 PLANTERS ON NORTH OF BLDG OK TO GROUT & CAP 2)HALF WALL AT WEST SIDE AND COLUMNS AT AUTO ENTRY OK TO GROUT |
|
06/11/2012 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
06/08/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 8'8" PALET RECYCLE KUFT ONLY / OK TO TOP OFF WITH SPECIAL INSPECTION GRID LINE 6-D 6-F 4-7 OK TO POUR |
|
06/07/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1ST LIFT ON COMPACTOR WALL |
|
06/06/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* STEM WALL @ BALL + PALLET RECYCLING AREA ONLY |
|
05/30/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
05/24/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) TOP RUN OF BLOCK ON NORTHWEST CORNER OF EXTERIOR OK FOR GROUT |
|
05/23/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) WOOD CAP ON EXTERIOR BLOCK OK 2) SHEATHING ON NORTH SIDE INTERIOR PARAPET OK 3) FRAMING ON NROTH SIDE PARAPET OK 4) TOP RUN OF BLOCK ON N.W. CORNER OF EXTERIOR OK TO GROUT |
|
05/17/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | 1) DRAINAGE AT AUTO CENTER OK (TRENCH) 2) OIOZO-BUILDOUT ON EAST SIDE OK TO CORRECT LAST LIFT 3) LOWER ROOF ON N SIDE OK - O1030 GLED/10 3RD LIFT, C-D/1 3RD LIFT. |
|
05/16/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
05/15/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
05/14/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
05/13/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
05/10/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: D.5-E.6/10 12' 8"; C.0/8.6-10 12' 8"; G.4-F.8/10 TOP OUT |
|
05/09/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: G.2/H.1/1.0 8' 8"; C.1/1.0 8' 8"; C.0/1.0-1.5; C.0/8.6-10.0 8' 8"; C.0-C.6/10.6 8' 8" D.5-E.6/10.0 8' 8" |
|
05/08/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: G.2-H.1/1.0 4' 8"; C.1/1.0 4' 8"; C.0/1.0-1.5 4' 8"; C.0/1.0-1.5 4' 8", C.0/8.6-10.0 4' 8"; C.0-C.6/10.0 4' 8"; D.5-E.6/10.0 4' 8"; K.0-L.0/6.2 4' 8" |
|
05/07/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: K-L/6.2 31' 4" |
|
05/04/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 4-6.2 TOP OUT AND K-L/4 TOP OUT |
|
05/03/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALLS AT 28' 8" GL: L/4.0-6.2; K-L/4; K-L/6.2 AT 31' 4"; K/6.2-7.5 AT 29' 4" AFF; K.0/1.6-2.2 AT 28' |
|
05/02/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL K/7.2-7.4 29' 4"; K/6.2-7. ? 29' 4"; K-L/6.2 24' 8"; L/4.0-6.2 24' 8"; K-L/4.0 24' 8"; K/1.6-4.0 24' 8" |
|
05/01/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: K-O/1.6-4.0 20' 8"; K-L/4.0 20' 8"; L/4.0-6.2-8.3 24' 8"; K/8.3-8.8 29' 4" J-K/8.8 24' 4"; J/S8-9.9 26' 8" |
|
04/30/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 4-6/L 16' 8", L-K/4 16' 8" 1.5-4/K 16' 8" |
|
04/27/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL 8.8-7.5/K 24' 8"; 6.2-4/4 16' 8"; 6.2/L-K 20' 8"; 6.2--7.5/K 20' 8" |
|
04/26/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALLS AT 12' 8" GL: L/4-6.2; K-L/4.0; K/1.6-2.4; AT 24' 8" GL: J/8.8-9.9 OK TO GROUT PROGRESS |
|
04/25/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALLS AT 20' 8" GL: K/7.9.9; J-K/9.9; J-K/7-8.8; CMU WALLS AT 16' 8" |
|
04/24/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: K.O/7.5-8.8 12' 8"; I.O-K.O/8.8 12' 8"-16' 8"; K.O-L.O/6.2 12' 8"; L.O/4.0-6.2 8' 8" |
|
04/23/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: J.0/8.8-9.9 16' 8" 6.2/K-L 8' 8"; 5-4/ ? 4' 8" L-K/4 4' 8" C/1.6-2.3 26' 8" |
|
04/20/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: C/1.2-2.3 24' 8"; 9.9-7/J-K 12' 8"; 1.5-4/K 4' 8" |
|
04/19/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
04/18/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* TOPOUT STEM AT COMPACTER 4' |
|
04/17/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* GL G.4-R/10 24'8", 8.3-9/L 20'8" |
|
04/16/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 8.8-9.9./J 8' 8"; 8.0-8.4/C 20' 8"; A.1-C/Z 12' 8";2-2.8/A.2 12' 8"; 4-5/B 12' 8" |
|
04/13/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 10.9/K.1-H.9-K.1 CORNER AT G.4/10 REPLACE, 9.2-7.6/A.1-6 TOP OUT, 5-6.9/B 12' 8", 4.5/A.Z 8' 8" |
|
04/12/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL D-C/10 TOP OUT, C/9-10 TOP OUT, 8/A.2-B.5 16' 8" C/1.5-2' 8' 5" ; 2-4/A.2 8' 5"; 2-4/A.2 8' 8" |
|
04/10/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 6.4-8.8/K 1ST LIFT; K-J/8.8 1ST LIFT; 8.8/10.0 1ST LIFT; H.9-H.1/10.8 24' 8" |
|
04/09/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 1.7-2.4/C-A.2 4' 8" LIFT |
|
04/06/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 9.9/K.1-J 24' 8"; 9.9-10.9/K.1 24' 8"; K.1-H.7/10.9 16' 8"; G-C.Z/10 TOP OUT ?-4/B.1 4' 8" |
|
04/06/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | 1) GL: 9.9/J.2-K.1; K.1/9.9-10.9 G.4/H; G.4/10.9-10 AT 24' TO 26'; C/1.5-2; A.2/2-2.8 AT 8'; B/4.6-6.9 AT 8'; 6.9-8.3/A.2 AT 4'' OK TO GROUT PROGRESS AREA | |
04/04/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: K-J/10.9 12' 8" NEED FIELD OBSERVATION OF ENGINEER ON FAILED WALL AT GL: G.4/10 2) NO DECKING INSTALL UNTIL APPROVED DIFFERED ? APPROVAL AND INSPECTION |
|
04/03/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. NEED ENGINEER TO FIX AT GL 6.4 / 9.9 CORNER 2. JOIST INSTALLER AT GL H.9-6.4 / 108 WITHOUT GROUT IN WALL 3. GL: C.2-F.8/10.0 24' 8"; G.4/10-10.8 24' 8" AND C/8.6-10 20' |
|
04/02/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
03/30/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 9.9/K.1-J 20' 8" |
|
03/29/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) PROGRESS AREA FIX V BRACKETS |
|
03/28/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 9.9/K.1-J ERD LIFT; K.1/9.9-10.9 12'; G.4/9.7-10.9 12'; F.3-C.0/10. 10'; C/9-10 16' |
|
03/23/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: ?-4 TOP OUT, 1-2 TOP OUT |
|
03/23/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | 1) GL: C-G/10, 3RD LIFT C/9-10 3RD LIFT, G-G.4/10 2ND LIFT, G.4/10-10.9 2ND LIFT, G.4-K.1/10.8 2ND LIFT, K.1/9.9-10.9 2ND LIFT, 9.9-K.1-J 2ND LIFT | |
03/22/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: G-K/1 TOP OUT, C-G/1 24' 8", K.1-J/10.9 1ST LIFT, H.9-G.4/4' LIFT, G.4/10-10.9 4' LIFT, C/8.6-10 4' LIFT |
|
03/21/2012 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
03/20/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: C-D.4/10 1ST LIFT |
|
03/16/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
03/15/2012 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
03/14/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: F.5-K.0/1.0 20' 8", E.8/F.3/1.0 AND C.3-D.0/1.0 16' 8" |
|
03/13/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) C-B.2/1.0 16' 8", 1.6-1.0/K 20' 8" |
|
03/12/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL F.5-K.0/1, K.0 1.0-1.4 16' 8" LIFT |
|
03/12/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | 1) GL: C.5/1.0, D.0/1.0 CANOPY 12' 8" AND C.0/1.0-1.6 16' 8" 2) NEED RFI ON CANOPY AT I BEAM AND DETAIL OF NELSON STUDS |
|
03/08/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) C-K/1.0 12' 8, C.O/1.0-1.6, K.O/1.0-1.4, A.5-C.0/4.1-10.0 |
|
03/07/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 1.0/C-K 2ND LIFT OK |
|
03/06/2012 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
03/05/2012 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
03/02/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL: 1/K-C 1ST LIFT,; C/1-2 1ST LIFT; K/1-2 1ST LIFT; |
|
02/29/2012 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL 6.6-8.8/K, 8.8/K-J, I/C-K |