Permit: T11CM02798

Parcel: 105102450


Addresses:

565 E WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM02798

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/06/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIXTURES ARE OK
2) SIGN CANOPIES NOT ON SIGN PERMIT OR INSTALLED PER ARTICLE 600
12/20/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) LETTER FOR GROUNDING IS NOT SUFFICIENT TO VERIFY EFFECTIVE GROUND FAULT PATH, NEED U.L. REQUIRED INSTRUCTIONS OR NRTL FIELD INSPECTION
2) NEED SIGN PERMIT AND PLANS ON SITE TO VERIFY CANOPIES
11/15/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
11/14/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
10/27/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE ON SITE
2) A REINSPECTION FEE MAY BE ASSESED
10/20/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOX ABOVE GRID LAYING ON CEILING-EXPOSED CONDUCTORS
2) SUPPORT WIRES NEEDED FOR LIGHTS
3) EXTENSION CORD USED FOR PERMANENT WIRING ABOVE CEILING
4) SUPPORT M/C CABLES PER 300.11-INDEPENDANT AND 334.30
5) WHERE IS FIXTURE GROUND WIRE
6) FINISH 3 & 4 PREVIOUS INSPECTIONS
10/13/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO RESCHEDULE FOR INTERIOR
2) OUTDOOR LIGHT TO BE WEATHER PROOF TO BOX
3) AWNINGS LISTED AS SIGNS-NEED TO BE INSTALLED PER ARTICLE 600: ISOLATE POWER TO DISCONNECTING MEANS, VERIFY BONDING 600.7 AND VERIFY POWER SUPPLY FOR LED'S
4) PLEASE HAVE SIGN PERMIT/PLANS ON SITE TO VERIFY WHICH PERMIT EQUIPMENT IS UNDER
09/28/2011 ELECTRIC - FINAL Denied 1) OUTDOOR LIGHT TO BE WEATHER PROOF TO BOX
2) NEED ELECTRICIAN PRESENT TO VERIFY WIRING METHODS FOR INTERIOR LIGHTING
3) EXPOSED CONDUCTORS EXTERIOR
4) FINISH AWNING LIGHTING