Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM02798
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/15/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIXTURE GROUNDS ADDED-APPEARS NO EFFECTIVE GROUND FAULT PATH-NEED INSTRUCTIONS 2) THHN IS NOT AN APPROVED SUPPORT METHOD 3) FINISH PREVIOUS ITEMS 1, 4, 5 AND 6 (3 & 4) 4) SUPPORT BOXES 5) PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
09/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK STORE FACE 2) BOX OVER FILLED-CHECK 3) SUPPORT BOXES ABOVE CEILING |
|
09/20/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CANNOT COVER BOXES-NEED ACCESS 2) NEED WET LOCATION WIRING METHOD 3) GROUND METAL BOXES 4) FILL UNUSED OPENINGS |