Permit: T11CM02696

Parcel: 12111364C


Addresses:

4745 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/19/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/16/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OPEN CEILINGS TO INSPECT WIRING FOR CUT IN BOXES
2) WHERE ARE NEW LIGHTS PER PLANS
3) SUPPORT BOXES ABOVE WALL
4) WHAT WIRING METHOD USES BARE CONDUCTORS IN RACEWAYS ?
5) SUPPORT VDV CABLING IN WALLS 725.8
6) BOX OVER FILLED
7) SUPPORT RACEWAYS PER CODE 358.30