3360 E SPEEDWAY BL


Inspection Status: Partial Approval

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM02454

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
09/21/2011 PLUMBING - ROUGH, SOIL Partial Approval REINSPECTED:
1) CONTRACTOR ADDED 2" ? VENT IN TRENCH AS RED LINED ON P-1
2) ABS DWV FOR MINOR REMODEL INSTALLED OK
3) ALL PIPING TO BE CAPPED OFF AT ALL TIMES
4) OK TO COVER
09/16/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) UABLE TO LOCATE APPROVED REVISION FOR UNDERGROUND
2) CONTRACTOR NOT SITE
3) PLUMBER NOT ON SITE
4) COINTINUED NOT READYS MAY RESULT IN A REINSPECTION FEE
09/14/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection 1) NOT INSTALLED PER APPROVED PLAN
2) BEFORE I CAN APPROVE A RED LINE OR AS BUILT IT MUST BE A PLAN THAT CAN BE APPROVED. LINE DRAWINGS WITH NO SIZES, DIMMENSIONS, DIRECTION OF FLOW, VENTING, ?, ETC...
09/13/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) MESSAGE DIDN'T RELATE WHAT NEEDED INSPECTION
2) CONTRACTOR AND PLUMBER NOT ON SITE