Permit: T11CM02309

Parcel: 10824011A


Addresses:

2450 E RIVER RD

Inspection Status: Approved

Inspection History: MECHANICAL - HYDRONIC PIPING

Date Description Inspector Results Comments
01/30/2012 MECHANICAL - HYDRONIC PIPING Approved IVRS - Inspection :*
01/05/2012 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI HYDRO TEST ON CHILLER PIPING UP TO ROOF OK TO INSULATE
2) 2 CONDENSATE DRAINS OK TO INSULATE
3) SUSPENDED ROUGH DUCT OK TO PROCEED
11/08/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI HYDRO TEST ON ALL UNDERGROUND PIPING OK TO COVER
11/07/2011 MECHANICAL - HYDRONIC PIPING Not ready for Inspection IVRS - Inspection :*
09/14/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI TEST OK ON PIPE IN TRENCH
2) PROVIDE A HYDRO STATIC TEST ON ALL HYDRONIC PIPING ON NEXT INSPECTION