Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T11CM02309
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/19/2012 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
01/30/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) VDV TO BE INDEPENDENTLY SUPPORTED 300.11 2) OK GROUNDING CONDUCTORS 3) OK WALL ABOVE MAIN VAULT PANEL 4) OK ABOVE CEILING 102-104, 107-109, 112-117 EXCEPT AS NOTED 5) OK POLE TO POLE PVC REPAIRS |
|
11/18/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) OK 20' #2 COPPER ATTACH TO REBAR |
|
09/30/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3RD LEVEL VAULT |
|
09/22/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 2ND LEVEL VAULT |
|
09/20/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 1ST LAYER PVC CONDUITS UNDER VAULT 2) EQUIPMENT TO BE LISTED AND LABELED |
|
09/13/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) WIRING METHOD NEEDS TO BE PER 517.13 (A) AND (B) 2) DISCUSSED WITH CONTRACTOR CODE APPLICATIONS |