Permit: T11CM02309

Parcel: 10824011A


Addresses:

2450 E RIVER RD

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
03/19/2012 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
01/30/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) VDV TO BE INDEPENDENTLY SUPPORTED 300.11
2) OK GROUNDING CONDUCTORS
3) OK WALL ABOVE MAIN VAULT PANEL
4) OK ABOVE CEILING 102-104, 107-109, 112-117 EXCEPT AS NOTED
5) OK POLE TO POLE PVC REPAIRS
11/18/2011 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) OK 20' #2 COPPER ATTACH TO REBAR
09/30/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 3RD LEVEL VAULT
09/22/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 2ND LEVEL VAULT
09/20/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 1ST LAYER PVC CONDUITS UNDER VAULT
2) EQUIPMENT TO BE LISTED AND LABELED
09/13/2011 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) WIRING METHOD NEEDS TO BE PER 517.13 (A) AND (B)
2) DISCUSSED WITH CONTRACTOR CODE APPLICATIONS