Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2011 | ELECTRIC - FINAL | Approved | PER INSP CARD | |
| 11/01/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANEL DIRECTORIES PER 408.4 2) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20, USE APPROVED RINGS 3) FIXTURES NOT FOR JUNCTION BOXES 4) LABEL WATER HEATER DISCONNECTING MEANS AND TIME CLOCKS |