Permit: T11CM02063

Parcel: 105110630

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/02/2011 ELECTRIC - FINAL Approved PER INSP CARD
11/01/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PANEL DIRECTORIES PER 408.4
2) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20, USE APPROVED RINGS
3) FIXTURES NOT FOR JUNCTION BOXES
4) LABEL WATER HEATER DISCONNECTING MEANS AND TIME CLOCKS