Permit: T11CM01971

Parcel: 11202003D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T11CM01971

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/05/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/18/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) BOXES MORE THAN 1/4" 314.20
2) NEED TO SEE EQUIPMENT ? 1, 2, 3 AND EXAM 10
3) PLEASE VERIFY GROUNDING FOR FLOOR BOXES PER 517.13
4) COUNTER RECEPTS ROOMS 2403 & 2407 TO BE GFCI PROTECTED
5) NEED ELECTRICIAN PRESENT TO OPEN PANEL
10/06/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK EXCEPT 2405, 2410
* VERIFY LISTING & LABELING OF EQUIPMENT