Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM01950
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) AIR BALANCE REPORT DOES NOT MEET MINIMUM AIR FLOW ON TU-4 AND TU-5 OVER ALL AIR FLOW IS COMFORTABLE 2) SOME T.U. UNITS (EXISTING) NTO PERFORMING AS SPECIFIED, THESE ARE BEING REPAIRED 3) PROVIDE REVISED AIR BALANCE REPORT TO MECH. ENGINEER FOR FINAL APPROVAL |