Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) AIR BALANCE REPORT DOES NOT MEET MINIMUM AIR FLOW ON TU-4 AND TU-5 OVER ALL AIR FLOW IS COMFORTABLE 2) SOME T.U. UNITS (EXISTING) NTO PERFORMING AS SPECIFIED, THESE ARE BEING REPAIRED 3) PROVIDE REVISED AIR BALANCE REPORT TO MECH. ENGINEER FOR FINAL APPROVAL |