Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T11CM01950

Parcel: 128102960

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM01950

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) AIR BALANCE REPORT DOES NOT MEET MINIMUM AIR FLOW ON TU-4 AND TU-5 OVER ALL AIR FLOW IS COMFORTABLE
2) SOME T.U. UNITS (EXISTING) NTO PERFORMING AS SPECIFIED, THESE ARE BEING REPAIRED
3) PROVIDE REVISED AIR BALANCE REPORT TO MECH. ENGINEER FOR FINAL APPROVAL