Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2011 | MECHANICAL - FINAL | Approved | ||
| 10/05/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/03/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) HP4 OVERFUSED 2) PROGRAM T-STATS SO FAN RUNS CONTINOUSLY, ALSO PROGRAM EXHAUST FANS 3) PROVIDE AIR BALANCE REPORT 4) PROVIDE 2" PLEATED FILTERS PER PLANS 5) TESTED DUCT SMOKE DETECTORS |