Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/27/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) LINE SET INSULATION STILL COATED AND DRIPPING WITH OIL, UNABLE TO DETERMINE IF LEAK IS STOPPED, REMOVE AND REPLACE INSULATION, MAKE SURE ALL GAPS IN INSULATION ARE SEALED, SO AS NOT TO CREATE CONDENATION 2) UNABLE TO IDENTIFY FUSE SIZE IN AIR HANDLER |
|
| 06/13/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A SECONDARY OVERFLOW SENSOR 2) PROVIDE A TRAP IN CONDENSATE DRAIN 3) PROVIDE PROPER SIZE FUSES 4) OIL LEAKING FROM LINE SET AT EVAP COIL 5) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 6) CONDENSOR OVERFUSED 7) PROVIDE FULL LENGTH SLEEPERS AT CONDENSOR |