Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T11CM01626

Parcel: 125081150

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/25/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/19/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HYDRONIC PIPING NOT SUPPORTED
2. SUPPLY & RETURN PLENUMS NOT ADEQUATELY SUPPORTED
3. NO SECONDARY DRAINS
4. FLEX DUCT LAYING ON CEILING AND CONDUITS
5. PROVIDE AIR BALANCE REPORT & DUCT SMOKE DETECTOR TEST