Permit: T11CM00993

Parcel: 10825287A


Addresses:

2404 E RIVER RD 02

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/06/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/21/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/20/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FLEX CAN NOT BE USED FOR LIGHTING PATIENT CARE AREAS CITY ADMEDMENTS OK DEVICE BOXES
2. USE CORRECT FITTING WITH M/C CABLE
3. VERIFY EXISTING RECEPTICAL MEET REQUIRMENTS 517.13
4. OPEN WALL FOR REWIRED RECEPTICAL EXAM #4 RMO
5. WHERE IS POWER FOR X-RAY EQUIPMENT
6. WHERE IS RELOCATED T-1?
7. WHERE IS PANEL SCHEDULE ?
04/19/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*