Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/20/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FLEX CAN NOT BE USED FOR LIGHTING PATIENT CARE AREAS CITY ADMEDMENTS OK DEVICE BOXES 2. USE CORRECT FITTING WITH M/C CABLE 3. VERIFY EXISTING RECEPTICAL MEET REQUIRMENTS 517.13 4. OPEN WALL FOR REWIRED RECEPTICAL EXAM #4 RMO 5. WHERE IS POWER FOR X-RAY EQUIPMENT 6. WHERE IS RELOCATED T-1? 7. WHERE IS PANEL SCHEDULE ? |
|
| 04/19/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |