Permit: T11CM00766

Parcel: 105110700


Addresses:

4320 N ORACLE RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM00766

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) DUCT SMOKE DETECTORS TESTED BY FIRE ALARM COMPANY
2) OK FOR FINAL
3) GAS FLEX CONNECTORS OK
09/13/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
09/09/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) GAS FLEX TO UNITS ON ROOF NOT SIZED CORRECTLY AS PER FLEX MANUFACTURERS DATA
2) NEED TO SEE DUCT SMOKE DETECTOR TEST REPORT
3) AIR BALANCE OK
4) EVERYTHING ELSE IS OK