Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) DUCT SMOKE DETECTORS TESTED BY FIRE ALARM COMPANY 2) OK FOR FINAL 3) GAS FLEX CONNECTORS OK |
|
| 09/13/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/09/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) GAS FLEX TO UNITS ON ROOF NOT SIZED CORRECTLY AS PER FLEX MANUFACTURERS DATA 2) NEED TO SEE DUCT SMOKE DETECTOR TEST REPORT 3) AIR BALANCE OK 4) EVERYTHING ELSE IS OK |