Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM00766
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/01/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE SESMIC RESTRAINTS ON ALL REGISTERS IN GRID CEILING 2) HORIZONTAL FLUE PIPING NOT TO EXCEED 75 PERCENT OF VERTICAL TOTAL LENGTH TO TERMINATION 3) PROVIDE T.D.C. CLIPS ON SUPPLY DUCT 4) PROVIDE SAMPLING TUBES IN RETURN DUCT |
|
06/16/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |