Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM00766
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/11/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK 116, 108, 102, 101A (PARTIAL) 101B, 101C, 103-107 AND 118 OK CORRECTIONS SALES FLOOR 2) FINISH FIRE ALARM 760.34 AND 300.11 3) FINISH WOMENS DRESSING LIGHTS |
|
08/10/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OPEN AREAS TO INSPECT |
|
08/05/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT RELOCATION M/C WHIPS AT 6' INTERVALS 2) SUPPORT UP OFF OF GRID 3) SUPPORT M/C WITHIN 12" OF BOXES 4) LEAVE OPEN AT WRAPS FOR POWER DROPS 5) OK ELECTRIC SALES FLOOR, EXCEPT AS NOTED 6) OK HARD LID ENTRY AREAS |
|
07/21/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK HARD LIDS BATHROOMS |