Permit: T11CM00766

Parcel: 105110700


Addresses:

4320 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/13/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/23/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK SWITCH BOARD CORRECTIONS
2) OK TO CLEAR TEC COMM
3) RECEIVED CHECK #3741 FOR $165.00 AFTER HOURS INSPECTION
07/18/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/15/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CONTRACTOR TO RECALL INSPECTION FOR MONDAY, WILL GO OVER POWER HOOK UP WITH RICK
07/13/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE ON SITE
07/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT END OF CONDUIT FROM SHARP METAL EDGE FOR VDV CABLES
2) IDENTIFY FIRE ALARM BOXES 760.10
3) OK WALLS 101, A, B, C-112, 114-116, 118 & 122
4) RECEIVED LETTER FOR M/C CABLE
06/28/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROPERLY INSTALL AND SUPPORT M/C AT TOP OF COLUMNS
2) NEED LETTER FOR M/C CABLING NOTES 19 AND 21 IN CONFLICT WITH PAGE 306.2 AND SECTION 260583.1.3 (D)
3) OK COLUMNS TO ROCK S.T.O.I.
06/21/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALL ROOM 113
06/20/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) EXTERIOR WALLS ROUGH SALES FLOOR AREA