Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM00617
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2012 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/28/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/26/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/25/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* INSULATE FREON LINES KINK IN DUCT FLEX JANITOR ROOM |
|
| 06/20/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/18/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR CONNON AREA ONLY |
|
| 06/13/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/11/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* PROVIDE FD ACCESS DOOR 3RD FLOOR OUR LAUNDRY FIX ALL GAPS IN LINE SET INSULATION |
|
| 06/05/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) 1ST 7 2ND FLOOR CORRIDORS OK |
|
| 06/04/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/01/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE 2" BEADED COLLARS AND SEAL HARD PIPE TO GRILLS |
|
| 05/29/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/04/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PVC TO BE PRIMED PRIOR TO GLUE, SUPPORTS NOT TO EXCEED 4', DO NOT STRAP TO DUCT 2) INSULATE BRANCH TAPS 3) PROVIDE ACCESS DOORS FOR DAMPER MOTORS |
|
| 04/25/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/09/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) O.S.A. DUCT NOT SEALED 2) PROVIDE ACCESS PANEL FOR FIRE DAMPER 3) PROVIDE ACCESS TO O.S.A. DAMPERS 4) PROVIDE DAMPERS IN O.S.A. 5) SYSTEMS NOT COMPLETE |
|
| 03/28/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/27/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |