Permit: T11CM00617

Parcel: 116206350


Addresses:

125 S LINDA AV


Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T11CM00617

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2012 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
06/21/2012 PLUMBING - ABOVE CEILING Partial Approval 1. Fifth floor corridor Ok to cover.
06/20/2012 PLUMBING - ABOVE CEILING Partial Approval 1. fifth floor corridor. Require overhead branch support. 2. Check for damaged, or unraveling insulation.
06/19/2012 PLUMBING - ABOVE CEILING Partial Approval 1. fourth floor corridor OK. 2. First floor flanges OK.
06/15/2012 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/13/2012 PLUMBING - ABOVE CEILING Partial Approval 1. third floor corridor: Some of the branch piping from the main is at the same elevation as the recessed cams. Piping may not be bent or straind, and clearances maintained above the light fixtures.
06/01/2012 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 1ST AND 2ND OK CORR
05/29/2012 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) INSULATE PIPING PER SECTION 220700 PLUMBING INSULATION (SPEC BOOK)
2) INSTALL HANGERS PER CHAPTER 2 2006 IPC, ALSO SEE 221116 3.7 HANGER LABEL PIPING PER 221116 3.?