Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T11CM00617
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2012 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/21/2012 | PLUMBING - ABOVE CEILING | Partial Approval | 1. Fifth floor corridor Ok to cover. | |
| 06/20/2012 | PLUMBING - ABOVE CEILING | Partial Approval | 1. fifth floor corridor. Require overhead branch support. 2. Check for damaged, or unraveling insulation. | |
| 06/19/2012 | PLUMBING - ABOVE CEILING | Partial Approval | 1. fourth floor corridor OK. 2. First floor flanges OK. | |
| 06/15/2012 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/13/2012 | PLUMBING - ABOVE CEILING | Partial Approval | 1. third floor corridor: Some of the branch piping from the main is at the same elevation as the recessed cams. Piping may not be bent or straind, and clearances maintained above the light fixtures. | |
| 06/01/2012 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) 1ST AND 2ND OK CORR |
|
| 05/29/2012 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) INSULATE PIPING PER SECTION 220700 PLUMBING INSULATION (SPEC BOOK) 2) INSTALL HANGERS PER CHAPTER 2 2006 IPC, ALSO SEE 221116 3.7 HANGER LABEL PIPING PER 221116 3.? |