Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/25/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) EM LIGHTING TO BE PER 700.12 (F) 2) DISCONNECTING MEANS FOR LIGHTS PER 410.73 (G) MENS BATH 3) RECEPT IN INDUSTRIAL COVERS MISSING SCREWS 406.4 (C) 4) FINISH 1 & 4 PREVIOUS ROOF: 1) MISSING WEST GFI 2) BROKEN GFI COVER EAST |
|
| 05/23/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |