Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/23/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOXES MORE THAN 1/4" 314.20 NEW DEVICES 2) VERIFY CONDUCTOR DERATING AT LIGHTING CONTROL PANEL 310.15 3) FILL UNUSED OPENING IN BOXES 4) REVISE PANEL DIRECTORIES 408.4 5) SECURELY ATTACH FIXTURES TO GRID 410.11 |
|
| 05/19/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH #1 PREVIOUS INSPECTION 2) FINISH BACK AREA 3) OK ELECTRIC AFTER CORRECTIONS-CHECK ON FINAL (SALES FLOOR) 4) RECEIVED LETTER FOR M/C CABLE |