Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2011 | ELECTRIC - UNDERGROUND | Approved | ||
| 05/09/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK RGS 90'S |
|
| 05/05/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 725.3 & 8, 800.3 & 24 AND 300.11 WILL APPLY 2) PROTECT PVC AT BASE PLATE 3) SUPPORT SENSOR WIRE IN WALL 725.8 4) PLANS CALL FOR 3/4" MINIMUM CONDUITS AND ? 90 DEGREE-NEED LETTER AUTHORIZING USAGE OF M/C CABLE AND PVC 90 DEGREE 5) SECURE M/C OR FLEX UPON EXIT OF WALL 6) OK STUD FRAMED WALLS SUBJECT TO LETTER |