| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2011 | ENGINEERING - FINAL | Approved | THE WEST PEDESTRIAN ACCESS RAMP DOES NOT MEET THE SLOPE SHOWN ON THE APPROVED PLAN, RAMP IS AT 9% AND THE SITE PLAN SHOWS 7% SLOPE. THE ENGINEER OF RECORD AND THE CITY OF TUCSON ENGINEERING REVIEWER (LAUREN MANKUS) STATED THAT AS LONG AS ONE ACCESS POINT MEETS ADA, THE WEST SIDE ACCESS RAMP CAN STAY AT ITS CURRENT SLOPE, AND THE ACCURATE ELEVATION MUST BE SHOWN ON THE AS-BUILT. ALL OTHER PUNCHLIST ITEMS LISTED HAVE BEEN ADDRESSED. APPROVED PER LAUREN MANKUS |
|
| 12/14/2011 | ENGINEERING - FINAL | Continued | SITE HAS GRADING PERMIT NOT FINALED #T11BU00531 | |
| 12/09/2011 | ENGINEERING - FINAL | Denied | 1) INSTALL WHEEL STOPS, STAKE IN PLACE. 2) INSTALL CLASS II BIKE PARKING PER PLAN. 3) INSTALL HC PARKING PER PLAN/ADAAG/ANSI. 4) REMOVE CONSTRUCTION DEBRIS/MATERIAL AWAY FROM PARKING AREA AND ACCESS. 5) REMOVE PORT-O-JON FROM PARKING AREA. 6) COMPLETE INSTALL OF STAIR- WELL RAILING. 7) MAIN ROOF DRAIN DUMPS DIRECTLY ONTO PEDESTRIAN ACCESS RAMP, CHANGE DIRECTION OF FLOW. 8) PEDESTRIAN ACCESS RAMP ON EAST SIDE, SLOPE IS AT 8.9%, PLANS SHOW 7%. ACCESS DOES NOT MEET ADAAG/ANSI. 9) PEDESTRIAN ACCESS RAMP ON THE WEST SIDE, SLOPE IS AT 9%, PLANS SHOW 7.2%. ACCESS DOES NOT MEET ADAAG/ANSI. |