Permit: T11CM00338

Parcel: 124010150


Addresses:

1245 E 2ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
12/08/2011 MECHANICAL - HOODS Approved IVRS - Inspection :*
08/17/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SMOKE CONTAINMENT TEST OK
2) BOTH INTERLOCK TEST OK
3) GREASE DUCT ACCESS CLEANOUTS NOT CORRECT SIZE
4) GREASE DUCT CLEANOUT ACCESS DOORS IN WRONG LOCATION
5) NO LIFE SAFETY ISSUES OBSERVED 1ST & 2ND FLOOR SHEET M15.1, EXCEPT ROOMS 104,116,210,212 AND 220
6) SEE BLDG INSPECTOR FOR TEMP C OF O FOR THIS AREA (ONLY)
08/15/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) I.D. ALL FAN COILS AND CONDENSORS
2) I.D. HEAT STRIPS ON DATA PLATES
3) 1ST LAYER OF FIRE WRAP OK
4) OK FOR 2ND LAYER
5) SEE BLDG INSPECTOR FOR TCO
08/11/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) CHECKED WELDS ON GREASE DUCT FROM HOOD TO OPENING IN WALL
2) OK FOR 1ST LAYER OF FIRE WRAP