Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2011 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 08/17/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) SMOKE CONTAINMENT TEST OK 2) BOTH INTERLOCK TEST OK 3) GREASE DUCT ACCESS CLEANOUTS NOT CORRECT SIZE 4) GREASE DUCT CLEANOUT ACCESS DOORS IN WRONG LOCATION 5) NO LIFE SAFETY ISSUES OBSERVED 1ST & 2ND FLOOR SHEET M15.1, EXCEPT ROOMS 104,116,210,212 AND 220 6) SEE BLDG INSPECTOR FOR TEMP C OF O FOR THIS AREA (ONLY) |
|
| 08/15/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) I.D. ALL FAN COILS AND CONDENSORS 2) I.D. HEAT STRIPS ON DATA PLATES 3) 1ST LAYER OF FIRE WRAP OK 4) OK FOR 2ND LAYER 5) SEE BLDG INSPECTOR FOR TCO |
|
| 08/11/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) CHECKED WELDS ON GREASE DUCT FROM HOOD TO OPENING IN WALL 2) OK FOR 1ST LAYER OF FIRE WRAP |