Permit: T11CM00338

Parcel: 124010150


Addresses:

1245 E 2ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
11/18/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
11/17/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection 1) FLEX DUCT NOT PROPERLY SUPPORTED, PROVIDE SADDLES
2) SEAL ALL DUCT, PROVIDE APPROVED TAPS
08/09/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1ST FLOOR:
1) EXTEND VENTS IN CONDENSATE DRAINS ABOVE DRAIN PANS
2) PROVIDE SECONDARY DRAINS
3) SUPPORT FLEX DUCT OFF OF GRID
4) PROVIDE TYPE I HOOD DUCTING
5) CONDENSATE OK TO INSULATE
07/28/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ROOMS 203 THRU 208 AND ROOM 213 DUCT ABOVE CEILING OK TO COVER
07/22/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) FLEX DUCT RESTRICTED AND DUCT NOT INSTALLED PER PLANS
2) REMOVE COMBUSTIBLE MATERIAL FROM PLENIUM
3) PROVIDE HIGH. E. BRANCH/FLEX TAPS PER PLANS