Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/17/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | 1) FLEX DUCT NOT PROPERLY SUPPORTED, PROVIDE SADDLES 2) SEAL ALL DUCT, PROVIDE APPROVED TAPS |
|
| 08/09/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR: 1) EXTEND VENTS IN CONDENSATE DRAINS ABOVE DRAIN PANS 2) PROVIDE SECONDARY DRAINS 3) SUPPORT FLEX DUCT OFF OF GRID 4) PROVIDE TYPE I HOOD DUCTING 5) CONDENSATE OK TO INSULATE |
|
| 07/28/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ROOMS 203 THRU 208 AND ROOM 213 DUCT ABOVE CEILING OK TO COVER |
|
| 07/22/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FLEX DUCT RESTRICTED AND DUCT NOT INSTALLED PER PLANS 2) REMOVE COMBUSTIBLE MATERIAL FROM PLENIUM 3) PROVIDE HIGH. E. BRANCH/FLEX TAPS PER PLANS |