Permit: T11CM00338

Parcel: 124010150


Addresses:

1245 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/06/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/05/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ALL ITEMS EXCEPT ROOF DONE
12/02/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
2) BREAKER LABELING 408.4
3) 314.21 NEED DRYWALL MUD
4) CHECK ROOF NEXT TIME
08/19/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TEMP LIGHTS BEING USED FOR EM LIGHTING WHILE ON BACK ORDER
1. WAITING ON SUMP PUMP LISTING
2. OUTSIDE EM - 700.12(F)
08/17/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED SUPPORT WIRES ON EXIT LIGHTS
2) MISSING EM
08/15/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*