Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/18/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK 2ND FLOOR 2) SEAL UNUSED CONDUIT OPENINGS |
|
| 10/12/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK HARD LIDS BATHROOM AND STORAGE 2) OK ELEVATOR LOBBY WALLS, LIDS AND ROOM 3) OK CANS SOFFIT, STAIRWELL EXTERIOR AND HALL |
|
| 08/19/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 2ND DECK PVC AND BOXES |
|
| 08/17/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NEED SUPPORT WIRES ON EXIT LIGHTS 2) MISSING EM CAN LIGHTS IN CAFE 3) PANEL DIRECTORIES TO BE PER 408.4. WHAT IS EXT ? 4) FINISH #1 & 5 PREVIOUS INSPECTION (GFI'S AND SUMP PUMP LISTING) 5) FINISH ARC SHIELDS 6) EM LIGHTS NOT WORKING 1ST FLOOR 7) FIXTURE DISCONNECTS 410.73 (G) 8) OK ABOVE CEILING ELECTRIC DINING 101 ROOF: 1) LOOSE FITTINGS 2) CANNOT USE SHEET METAL THREAD SCREWS GROUNDING 250.8 3) SUPPORT SEAL TITE |
|
| 08/15/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL KITCHEN RECEPTS 210.8 GFCI PROTECTED 2) LABEL DISCONNECTS 3) BOXES MORE THAN 1/4" AND 1/8" 314.20 AND 314.21 4) FINISH ELECTRIC AND PREVIOUS ITEMS 5) VERIFY LISTING ON SUMP PUMP |
|
| 08/09/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 2) VDV CABLING TO BE INDEPENDENTLY SUPPORTED 300.11 AND 725.8 3) NEED SUPPORT WIRES ALL FIXTURES 4) FINISH HOLD INTER LOCK 5) PROPERLY SUPPORT CAN BATH HALL DOWN 6) OK 2 X 4 FIXTURES 7) DO NOT CLOSE |
|
| 08/05/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/22/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED CONDUIT OPENINGS 2) OK 203-208, 213, 214 AND 212 3) RECEIVED LETTER FOR CONDUIT SIZES |