Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2ND FLOOR WALLS |
|
| 08/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS LUNGE 202 & 108 2) OK VDV 101, 109, 111 & 102 |
|
| 07/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK RM 103 CAFE SUBJECT TO LETTER |
|
| 07/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 208,212,105-107 AND 109 SUBJECT TO LETTER |
|
| 06/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED OPENINGS IN BOXES AND PANEL 2) PROVIDE BACK SUPPORT 312.23 3) PLANS CALL FOR 3/4" MINIMUM CONDUIT-NEED LETTER FROM ENGINEER AUTHORIZING 1/2" CONDUIT 4) OK WALLS 203-207, 213 AND 214 SUBJECT TO LETTER AND COMPLETION OF CORRECTIONS |