Permit: T11CM00170

Parcel: 125073400


Addresses:

2228 E 6TH ST

Inspection Status: Denied

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/25/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED HEADER AT WINDOW
2) NEED ANCHOR BOLTS ADDED TO SOLE PLATES
3) NEED WATER HAMMERS ON HOT/COLD WASHING MACHINE
4) NO P-TRAP AT LAUNDRY STAND PIPE (ADD ONE)
5) B-VENT NEEDS MINIMUM 1" CLEARANCE TO COMBUSTIBLES
6) FILL ALL HOLES IN JOIST HANGERS AND H2.5 CONNECTIONS
7) PROVIDE COMBUSTION VENTS FOR GAS WATER HEATER
8) EXTEND B-VENT ABOVE ROOF MINIMUM 2' FT
9) EXTERIOR SIDING LOOSE NEEDS TO BE NAILED CODE MINIMUM 6" EDGES 12" FIELD