Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HYDRONIC PIPING
Permit Number - T11CM00159
Inspection Description - MECHANICAL - HYDRONIC PIPING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2012 | MECHANICAL - HYDRONIC PIPING | Approved | IVRS - Inspection :* | |
01/30/2012 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) NO BODY ON SITE |
|
01/23/2012 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 3RD AND 4TH FLOOR PATCHING COMPLETED |
|
01/11/2012 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) FIRE CAULKING FLOORS 1 & 2 OK 2) DRYWALL PATCHING IS PROGRESSING |
|
01/03/2012 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR INSULATING COMPLETE 2) STILL NEED FIRE CAULK AND PATCHING |
|
12/28/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR SOUTH AND WEST CORRIDOR UNITS INSULATION OK, REPAIR ALL OPENINGS IN DRAFT STOP ABOVE CEILING FIRE CAULK NOT COMPLETE |
|
12/16/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) ALL OPENINGS IN DRAFT STOP WITHIN RETURN AIR PLENIUMNS MUST BE REPAIRED-NO EXCEPTIONS 2) 2ND FLOOR INSULATING AND FIRE CAULK COMPLETE |
|
12/15/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
12/13/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 3RD FLOOR COMPLETE |
|
12/06/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) STILL NEED FIRE CAULKING 4TH FLOOR |
|
12/02/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 4TH FLOOR INSULATION PROGRESSING |
|
11/30/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
11/14/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE BREEZEWAY PIPING |
|
11/10/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
11/09/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
11/04/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
11/03/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) HYDRO PIPING FROM MECHANICAL ROOM TO ASSISTED LIVING OK TO INSULATE |
|
10/27/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) INSULATION MAINS IN ASSISTED LIVING DINING ROOM OK 2) 4TH FLOOR FAN COIL PIPING PROGRESSING 3) NEED TO SEE INSULATION |
|
10/26/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
10/25/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 100 PSI TEST ON MAIN PIPING IN ASSISTED LIVING BLDG 2) UP TO EXERCISE EOOK OK TON INULATE |
|
05/20/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) BLDG "C" AND "D", MAINS THROUGH CORRIDORS TO STUB OUT IN ROOMS PRESSURE TEST OK AT 100 PSI. OK TO INSULATE IN CORRIDORS |
|
05/13/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) ALL MAIN PIPING IN MAIN BLDG OK FOR INSULATION UP TO EXISTING PIPING |
|
05/11/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR CORRIDORS OK FOR INSULATION 2) 100 PSI HYDRO TEST OK |
|
05/04/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 2ND FLOOR OK TO INSULATE 2) ALL RISERS OK TO INSULATE TO THE 1ST FLOOR EXCEPT SOUTH EAST-OK 4TH THRU 2ND 3) 100 PSI TEST OK |
|
05/02/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* OK TO INSULATE ALL 3RD FLOOR PIPING. 2ND FLOOR NE CORRIDOR OK FOR INSULATION 100PSI TEST OK |
|
04/29/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
04/26/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
04/18/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* |