Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2010 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 10/15/2010 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE A GAGE W 1/10 PSI INCRIMINTATIONS: ( 15 ) , AND PROVIDE A MIN OF 10 PSI. CORRECT DAMAGED WH PLATFORM, BUILD + CODE STANDARDS OR PROVIDE A LISTED WH PLATFORM. NOTE WOOD REQUIRED A DRAIN PAN INSTALL TYPE B VENT ABU ON CLOSURE, W/ ALL FITTINGS IN CORRECT DIRECTION OF FLOW. WASTE SUPPLY REQ A SHUT IFF VALVE. SUPPORT / SECURE ALL PIPING PROVIDE ELECTRICAL BONDING OF GAS SYSTEM |