Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10OT01724

Parcel: 10706045A

Inspection Status: Denied

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
04/07/2011 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NM CABLE AND CONDUCTOR IN DETERIORATED CONDITION-NM NOT FOR WET LOCATION
2) BURIAL DEPTH TO BE PER 300.5
3) PROTECT CONDUCTOR FROM SHARP EDGES 300.4 AND USE APPROVED FITTINGS
4) CONDUCTOR TO AMPACITY OF CIRCUIT
5) HAND HOLE NOT LARGE ENOUGH TO WORK IN
6) BOND POLE AND BOX
7) DISCONNECT ON WALL NOT INSTALLED TO CODE-WHAT IS DISCONNECT FOR ?
8) VERIFY SIGN CIRCUIT FOR 600.5
04/06/2011 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*