Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL JOINTS TO BE PRIMED, PRIMER IS TO BE PURPLE IN COLOR 2) ALL DUCT WITHIN MECH-CLOSET IS TO BE INSULATED 3) CORD CONNECTOR AT INDOOR UNIT IS LOOSE 4) PROVIDE TIGHT FITTING JOINTS ON FLUE PIPING, MINIMUM 1" INSERTION AT ALL JOINTS, B-VENT THRU WALL NOT PROPERLY INSTALLED 5) PROVIDE SERVICE OUTLET ON ROOF WITHIN 25' OF UNIT |
|
| 09/29/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |