Permit: T10ME00589

Parcel: 108201330


Addresses:

1255 E PASEO ALEGRE

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/20/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PVC TO TERMINATE 6" ABOVE GRADE
2) PVC TO BE U.V. COATED
3) CONDENSATE TRAP INSTALLED WRONG, VENT ON WORNG SIDE
4) BLACK WIRE NOT TO BE USED AS GROUND
5) ALL PVC JOINTS ARE TO BE PRIMED, ALL PRIMER IS TO BE PURPLE IN COLOR
6) PROVIDE SERVICE OUTLET WITHIN 25' OF UNIT AT SAME LEVEL