Case: T10FR02417

Parcel: 12402034D


Addresses:

1701 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
01/20/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
11/18/2010 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6 Operations and maintenance. Commercial
cooking systems shall be operated and maintained in accordance
with this section.

____I NEED A COPY OF YOUR HOOD SYSTEM INSPECTION REPORT. MAKE SURE ALL NOTED DEFICIENCIES HAVE BEEN CORRECTED.
11/18/2010 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.7 Separation. All deep-fat fryers shall be installed with at
least a 16 inch space between fryer and surface flames of
adjacent cooking appliances.
Exception: Where a steel or tempered glass baffle plate is
installed at a minimum 8 inches in height between the fryer and
surface flames of the adjacent cooking appliance, the
requirement for a 16 inch space shall not apply. Where the
fryer and the surface flames of the adjacent cooking applicance
are at different horizontal planes, the minimum height of 8 inches
shall be measured from the higher of the two.

____PROVIDE THE PROPER SEPARATION OR BAFFLE PLATE. A BAFFLE PLATE CANNOT BE TEMPORARY. IT MUST BE INSTALLED AND PERMANENT.
11/18/2010 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.

____CAPS NEEDED FOR FIRE DEPARTMENT CONNECTIONS ON WEST SIDE OF BUILDING.
____SERVICE AND TAG STANDPIPE SYSTEM. YOU MUST FILE A PETITION OF APPEAL TO THE FIRE MARSHAL IF YOU WISH TO ELIMINATE YOUR HOSE CABINETS. YOU CAN INCLUDE THE ELIMINATION OF THE FIRE EXTINGUISHER CABINETS IN THE SAME APPEAL.
11/18/2010 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____EITHER SERVICE AND MOUNT EXTRA EXTINGUISHERS IN DINING ROOM OR STORE THEM OUT OF SIGHT.
____SERVICE AND TAG EXTINGUISHER IN KITCHEN.
____REPLACE ALL MISSING EXTINGUISHERS IN EXTINGUISHER CABINETS. EXTINGUISHERS ARE NOT REQUIRED IN YOUR OCCUPANCY BUT IF YOU HAVE THE CABINETS THEN YOU MUST KEEP EXTINGUISHERS INSIDE OF THEM.