Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/18/2010

Applicant:

TUCSON DELTA CHI ALUMNI BOARD

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02417
Case Description: INSPECTION
Total Completed Inspections - 7
End Date Description Inspector Results Comments
11/18/2010 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____EITHER SERVICE AND MOUNT EXTRA EXTINGUISHERS IN DINING ROOM OR STORE THEM OUT OF SIGHT. ____SERVICE AND TAG EXTINGUISHER IN KITCHEN. ____REPLACE ALL MISSING EXTINGUISHERS IN EXTINGUISHER CABINETS. EXTINGUISHERS ARE NOT REQUIRED IN YOUR OCCUPANCY BUT IF YOU HAVE THE CABINETS THEN YOU MUST KEEP EXTINGUISHERS INSIDE OF THEM.
11/18/2010 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____CAPS NEEDED FOR FIRE DEPARTMENT CONNECTIONS ON WEST SIDE OF BUILDING. ____SERVICE AND TAG STANDPIPE SYSTEM. YOU MUST FILE A PETITION OF APPEAL TO THE FIRE MARSHAL IF YOU WISH TO ELIMINATE YOUR HOSE CABINETS. YOU CAN INCLUDE THE ELIMINATION OF THE FIRE EXTINGUISHER CABINETS IN THE SAME APPEAL.
11/18/2010 VIOL - MEANS OF EGRESS JVINCENT Approved 1027.5 Illumination emergency power. ____REPLACE MISSING EMERGENCY LIGHTING UNIT. 2ND FLOOR HALL NEXT TO ROOM #19.
11/18/2010 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 904.11.7 Separation. All deep-fat fryers shall be installed with at least a 16 inch space between fryer and surface flames of adjacent cooking appliances. Exception: Where a steel or tempered glass baffle plate is installed at a minimum 8 inches in height between the fryer and surface flames of the adjacent cooking appliance, the requirement for a 16 inch space shall not apply. Where the fryer and the surface flames of the adjacent cooking applicance are at different horizontal planes, the minimum height of 8 inches shall be measured from the higher of the two. ____PROVIDE THE PROPER SEPARATION OR BAFFLE PLATE. A BAFFLE PLATE CANNOT BE TEMPORARY. IT MUST BE INSTALLED AND PERMANENT.
11/18/2010 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. ____I NEED A COPY OF YOUR HOOD SYSTEM INSPECTION REPORT. MAKE SURE ALL NOTED DEFICIENCIES HAVE BEEN CORRECTED.
11/18/2010 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Approved 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ____EXPOSED ELECTRICAL IN FOYER. CAP CONDUIT. ____INSTALL "BLANK" IN ELECTRICAL PANEL. BASEMENT. ____COVER NEEDED FOR LIGHT SWITCH IN POOL ROOM.
11/18/2010 INSP - FULL JVINCENT Approved FULL FIRE INSPECTION SPRINKLER FINAL 8/6/10 FIRE ALARM FINAL 8/9/10