Case: T10FR02392

Parcel: 130140280


Addresses:

4040 E 22ND ST

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
11/08/2010 INSP - FULL Violation _____ Exit Sign Illumination - Front door (repair or replace) -

____ ____ Banquet Room Exit Signs (x2)

_____ Repair Emergency Light - Banquet Room -

_____ BR Hall - _____ Kitchen

_____ check and repair all others as necessary

_____

_____ Clean grease accumulation on fryers and hoses

TFC 1008.1.8.4 - Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

_____ Remove hasp locking device from kitchen exit door

TFC 605.6 - Unapproved conditions.
Open junction boxes and open-wiring splices shall be prohibited.

_____ Replace filters to protect exposed wiring in Icemaker

_____ Replace knock-outs in electrical panel

_____ Replace cover and conduit for electrical wiring penetrating hood back-splash and seal.

TFC 605.4.2 - Power supply.
Relocatable power taps shall be directly connected to a permanently installed receptacle.

_____ Plug office power strip directly into wall outlet.

TFC 605.7 - Appliances.
Electrical appliances and fixtures shall be tested and listed in published reports of inspected electrical equipment by an approved agency and installed and maintained in accordance with all instructions included as part of such listing.

_____ Power cord servicing timer under hood shall be replaced by licenced electrician so as to maintain it's listing. Provde a recipt so such repair.