Case: T10FR02327

Parcel: 124161130


Addresses:

1300 S PARK AV

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
11/04/2010 VIOL - MEANS OF EGRESS Correction Required 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official.

1___ SOUTHEAST EXIT DOOR IN SOUTH ROOM EXIT MUST BE CLEAR AT ALL TIMES NEED TO REMOVE BINS.
2___ EXIT DOOR IN NORTHWEST ROOM NEEDS TO BE CLEAR AT ALL TIMES.
11/04/2010 VIOL - MEANS OF EGRESS Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system

1___ REPAIR EMERGENCY LIGHT ON WEST WALL IN NOTHWEST PAPER STORAGE ROOM.
2___ REPAIR EMERGENCY LIGHT IN NORTH STAIRWELL.
3___ REPAIR EMERGENCY LIGHT IN SOUTH STAIRWELL