Case: T10FR02327
Case Details
Entered Date:
11/04/2010
Applicant:
JENICA ENTERPRISES LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T10FR02327
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2010 | INSP - FULL | WMOTTO | Correction Required | PLEASE CORRECT TUCSON FIRE CODE VIOLATIONS. |
| 11/04/2010 | VIOL - PRECAUTION AGAINST FIRE | WMOTTO | Correction Required | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1___ NEED TO REMOVE STORAGE IN NORTHWEST ROOM TO ASSURE 18 INCHES BELOW SPRINKLER HEADS. |
| 11/04/2010 | VIOL - FIRE SERVICE FEATURES | WMOTTO | Correction Required | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. 1___ NEED TO CLEAR OBSTACLES IN SPRINKLER RISER ROOM. |
| 11/04/2010 | VIOL - FIRE SERVICE FEATURES | WMOTTO | Correction Required | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. 1___NEED TO LABEL SPRINKLER RISER ROOM DOOR WITH A SIGN ON DOOR. |
| 11/04/2010 | VIOL - FIRE RESIST.RATED CONST | WMOTTO | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. 1___ NEED TO HAVE CEILING TILES PLACED BACK IN THERE NORMAL POSITIONS. |
| 11/04/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___ NEED TO HAVE ALL FIRE EXTINGUISHERS SERVICED AND TAGGED. |
| 11/04/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 1___ NEED TO HANG EXTINGUISHER IN SOUTH ROOM 2___ NEED PROVIDE SPRINKLER REPORT SHOWING SYSTEM HAS BEEN SERVICED WITHIN THE YEAR WITH NO DEFICIENCIES. ALL DEFICIENCIES FROM REPORT ON2/5/2009 MUST BE REPAIRED. |
| 11/04/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system 1___ REPAIR EMERGENCY LIGHT ON WEST WALL IN NOTHWEST PAPER STORAGE ROOM. 2___ REPAIR EMERGENCY LIGHT IN NORTH STAIRWELL. 3___ REPAIR EMERGENCY LIGHT IN SOUTH STAIRWELL |
| 11/04/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. 1___ SOUTHEAST EXIT DOOR IN SOUTH ROOM EXIT MUST BE CLEAR AT ALL TIMES NEED TO REMOVE BINS. 2___ EXIT DOOR IN NORTHWEST ROOM NEEDS TO BE CLEAR AT ALL TIMES. |