Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01688

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2010 INSP - FULL Approved
08/11/2010 INSP - FULL Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

" Replace the cover on the junction box.
08/11/2010 INSP - FULL Correction Required 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.

" Maintain the area in front of the breaker panels.
08/11/2010 INSP - FULL Correction Required 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.

" Remove the extension cord on the coffee machine. Only power strips or permanent wiring may be used.
08/11/2010 INSP - FULL Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.

" Repair the wall in the storage area to prevent the travel of smoke and flame in case of a fire.